DSpace Repository

EXPERIMENTAL AND NUMERICAL ANALYSIS OF AIR CONDITIONING SYSTEM USING MICROCHANNEL HEAT EXCHANGER

Show simple item record

dc.contributor.author Abhijith, K R
dc.contributor.author Mohammed, Sadhikh
dc.date.accessioned 2022-09-24T05:58:33Z
dc.date.available 2022-09-24T05:58:33Z
dc.date.issued 2022-12-12
dc.identifier.uri http://210.212.227.212:8080/xmlui/handle/123456789/164
dc.description.abstract The potential performance enhancement of a residential split air conditioning system with a microchannel heat exchanger is investigated numerically and verified experimentally. Replacement of fin and tube condenser in the air conditioning system with a microchannel condenser is studied. Numerical analysis of refrigerant flow through microchannel is done and the results shows that the microchannel offers a higher volumetric heat exchange capacity with increased heat transfer area due to the cross section with hydraulic diameter of micrometre range. A residential split air conditioning system of 2 TR cooling capacity with fin and tube condenser and refrigerant R22 is considered for the analysis. The system's numerical and experimental performance analysis is done, and the potential replacement of the fin and tube condenser with a microchannel condenser of the exact dimensions is analysed. The heat duty of the condenser is increased by 82% when the microchannel heat exchanger is installed. Numerical analysis shows that the COP of the system can be improved by 16% by replacing the fin and tube condenser with a microchannel condenser. The microchannel condenser can reduce the overall weight of the outdoor unit since it is compact and 38% lighter than the ordinary bulky fin and tube condenser. en_US
dc.description.abstract The potential performance enhancement of a residential split air conditioning system with a microchannel heat exchanger is investigated numerically and verified experimentally. Replacement of fin and tube condenser in the air conditioning system with a microchannel condenser is studied. Numerical analysis of refrigerant flow through microchannel is done and the results shows that the microchannel offers a higher volumetric heat exchange capacity with increased heat transfer area due to the cross section with hydraulic diameter of micrometre range. A residential split air conditioning system of 2 TR cooling capacity with fin and tube condenser and refrigerant R22 is considered for the analysis. The system's numerical and experimental performance analysis is done, and the potential replacement of the fin and tube condenser with a microchannel condenser of the exact dimensions is analysed. The heat duty of the condenser is increased by 82% when the microchannel heat exchanger is installed. Numerical analysis shows that the COP of the system can be improved by 16% by replacing the fin and tube condenser with a microchannel condenser. The microchannel condenser can reduce the overall weight of the outdoor unit since it is compact and 38% lighter than the ordinary bulky fin and tube condenser. en_US
dc.language.iso en en_US
dc.relation.ispartofseries ;TKM20MEIR01
dc.subject Microchannel condenser en_US
dc.subject Microchannel condenser en_US
dc.subject Coefficient of Performance (COP) en_US
dc.subject Coefficient of Performance (COP) en_US
dc.subject Air conditioning system en_US
dc.subject Air conditioning system en_US
dc.subject Heat transfer en_US
dc.subject Heat transfer en_US
dc.subject R22 en_US
dc.subject R22 en_US
dc.title EXPERIMENTAL AND NUMERICAL ANALYSIS OF AIR CONDITIONING SYSTEM USING MICROCHANNEL HEAT EXCHANGER en_US